Default value = 0%
Outside air damper minimum position.
Will be active only when fan is on ( G terminal ) and the
internal or remote scheduling is in occupied mode.
When internal or remote scheduling is in unoccupied mode
and/or fan is off, minimum position will be set to 0%
0 to 100 % = 0 to 10 Vdc output range
Mechanical cooling allowed
Default value = Off
Allows the operation of the mechanical cooling if the free
cooling ( economizer ) cannot maintain the cooling setpoint.
Off Typically applies when the MS ( mixed air temperature
sensor ) is installed after the mechanical cooling refrigeration
coils. In this case, mechanical cooling will never operate at the
same time as free cooling.
On Typically applies when the MS ( mixed air temperature
sensor ) is installed before the mechanical cooling
refrigeration coils in the mixing plenum. In this case,
mechanical cooling is allowed when the free cooling (
economizer operation ) cannot maintain the cooling setpoint.
Default value = 55 °F ( 13.0 °C )
Free cooling mixed air setpoint when economizer mode is
enabled.
50 to 90 °F ( 10.0 to 32.0 °C )
Display mixed air temperature
Economizer model only, only if sensor
Used as diagnostic / service help to troubleshoot and
diagnose economizer operation.
10%
Setting for 0-10
Vdc Actuator
10%
Setting for 2-10
Vdc Actuator
28%