H) Clock/Day Settings
Clock
set Y/N
This section of the menu permits the user to set the time and day.
Time setting Day setting Time format setting
Time
set? Y/N
No next
Yes down
Day
set? Y/N
No next
Yes down
12/24hrs
set? Y/N
No = exit
Yes down
Time
0:00
Use ▲▼
To set value
Day
Monday
Use ▲▼
To set value
12/24hrs
12 hrs
Use ▲▼
To set value
Installer configuration parameter menu
- Configuration can be done through the network or locally at the thermostat.
- To enter configuration, press and hold the middle button “Menu for 8 seconds
- If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down” arrows and pressYes” to gain
access to all configuration properties of the thermostat. A wrong password entered will prevent local access to the configuration menu.
- Once in the configuration menu, press the “No” button repetitively to scroll between all the available parameters.
- When the desired parameter is displayed, press “Yes” to adjust it to the desired value using “up” and “down” arrows. Once set, press
Yes” to scroll to the next parameter.
Configuration
parameters
Significance
Default value
Adjustments
Pswrd
Configuration parameters menu access
password
Default value = 0 ( no password
prompted )
This parameter sets a protective access password to
prevent unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu.
Range is: 0 to 1000
Com addr
Thermostat networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models
Conditional parameter to Wireless models
This parameter will only appear when a BACnet or
wireless network adapter is present. If the thermostat is
installed with a LonWorks
adapter, this parameter will not
be used or displayed
- For BACnet MS-TP models valid range to use is
from 1 to 127. Default value of 254 disables BACnet
communication for the thermostat.
- For wireless models valid range is 0 to 254 with a
maximum of 30 thermostat per EC-BOS
PAN ID
Personal Area Network Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models
This parameter will only appear when a wireless network
adapter is present. If the thermostat is installed with a
BACnet or LonWorks adapter, this parameter will not be
used or displayed
This parameter (Personal Area Network Identification) is
used to link specific thermostats to a single specific
wireless gateway ( EC-BOS ) For every thermostat
reporting to a gateway ( maximum of 30 thermostats per
gateway ), be sure you set the SAME PAN ID value both
at the gateway and the thermostat(s).
The default value of 0 is NOT a valid PAN ID.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls RT Series and is the answer not in the manual?

Distech Controls RT Series Specifications

General IconGeneral
BrandDistech Controls
ModelRT Series
CategoryThermostat
LanguageEnglish

Related product manuals