XTL/XTLC Installation Guide Digital Monitoring Products
7
COMPLIANCE
Listed Compliance Specications
15.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theXTL/XTLCinaccordancewithanyoftheANSIorSIAburglarystandards.Additionalspecicationsmaybe
required by a particular standard.
15.2 Use Marking
CommercialCentralStation,HouseholdBurglarandFireControlUnit.
15.3 NFPA 72
ThisequipmentshouldbeinstalledinaccordancewithChapter11oftheNationalFireAlarmCode,
ANSI/NFPA72-2002,(NationalFireProtectionAssociation,BatterymarchPark,Quincy,MA02269).Printed
information describing proper installation, operation, testing, maintenance, evacuation planning, and repair
serviceistobeprovidedwiththisequipment.Warning:Owner’sinstructionnotice,nottoberemovedby
anyone except occupant.
15.4 Types Of Service
SuitableforCentralStationCellular.SuitableforHouseholdFireandHouseholdBurglary.Testweekly.
15.5 Bypass Reports
ThebypassreportsmustbeprogrammedasYESforalllistedburglaryapplications.
15.6 Battery Standby
TheXTL/XTLCisshippedwithabatteryfor24hourbatterystandbyoperation.
Household Burglar-Alarm System Units
ANSI/UL 1023
16.1 Bell Cutoff
Thebellcutofftimecannotbelessthan4minutes.
16.2 Entry Delay
Themaximumentrydelayusedmustnotbemorethan45seconds.
16.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
16.4 Wireless External Contact
Whenused,theExternalContactof1101,1102,or1105transmittersmustbeprogrammedNormallyClosed.
16.5 Wireless Supervision Time
TheZoneInformationSupervisionTimecannotbesetto0(zero).
16.6 Wireless Audible Annunciation
TheWirelessAudibleoptionmustbeselectedasDAYforresidentialapplications.
16.7 Panel location
Mountpanelinsideprotectedarea.
16.8 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.