CapTouch Cabin Control Operation
Parameter Name DX CW Factory Default Parameter Range
P-30 Wi-Fi Connectivity
x x DIS
Available only in Wi-Fi capable displays, indicated by the Wi-Fi icon on the display. Refer to “Using the
CapTouch Wi-Fi Application” on page 21 for detail on the full functionality of the Wi-Fi capability.
P-31
Seawater Low-Limit
Adjustment
x 40°F (4°C) 35°F to 50°F (2°C to 10°C)
If the optional seawater low-limit adjustment sensor is connected to the control board H2O Out 2-pin
plug, set the system to switch from reverse-cycle heat to auxiliary electric heat (if an auxiliary electric
heater is installed and enabled).
Adjustment occurs when the seawater temperature drops below 40 °F (4 °C) and the reverse-cycle
heat has been in operation for more than five minutes. Once the seawater rises 3°F above the
seawater low-limit adjustment sensor temperature set point, the system returns to reverse-cycle
heating.
If an auxiliary electric heater is not installed, the system will shut down and flash LO then SE when the
seawater drops below 40°F (4°C) (default). Once the seawater rises 3°F above the seawater low-
limit adjustment sensor temperature set point, the system automatically goes back into reverse-cycle
heating and stops flashing LO then SE.
P-32
Humidity Sensor
Calibration
x x
Ambient Relative
Humidity
Ambient Relative Humidity ±10%
Calibrate the room temperature/relative humidity combination sensor to display the correct room
humidity reading.
I
This setting is applicable to soware revision #42 and newer only.
P-33
Water Inlet Temperature
Sensor Calibration
x x
CW = Supplied
Chilled Water
Temperature
DX = Condenser Coil
or Seawater
Temperature
CW = Supplied Chilled Water Temperature ±10°F (6°C)
DX = Condenser Coil or Seawater Temperature
±10°F (6°C)
Calibrate the Water Out (DX) or Water In (CW) temperature sensor to display the correct water
temperature reading. The setting increments are in °F even when the control is set to display °C.
I
This setting is applicable to soware revision #42 and newer only.
P-34 OAT Sensor Calibration
x x
Outside Ambient
Temperature
Outside Ambient Temperature ±10°F (6°C)
Calibrate the outside ambient air temperature sensor to display the correct outside air temperature
reading. The setting increments are in °F even when the control is set to display °C.
I
This setting is applicable to soware revision #42 and newer only.
7.4.3 Exiting programming mode
To exit the programming menu manually, simultaneously
tap and hold the Up (+) and Mode icons for three
seconds until the room temperature is displayed.
Alternatively, the display automatically exits the
programming menu aer 10 seconds of inactivity.
The control’s soware version (such as “40”) appears
in the display for one second prior to the manual or
automatic exit from the programming mode. The control
enters OFF mode aer exit.