Programming MCS T6, MCS T12, MCS T16
18
P-9 High Water Temperature
Limit (°F)
OFF 100 – 150
P-10 Display Brightness
Control
9 4 = Low
13 = Maximum
P-11
Display
º
F or
º
C
F F = Fahrenheit displayed
C = Celsius displayed
P-12 Cycle Pump With
Compressor or
Continuous Pump
OFF OFF = Cycle with compressor
On = Continuous pump
P-13 Reverse Fan Speeds Dur-
ing Heating Mode
rEF nor = Normal fan operation
rEF = Reversed fan in heating
P-14 Continuous Fan or Cycle
Fan with Compressor
con CYC = Cycle fan with compressor
con = Continuous fan operation
P-15 Reverse Cycle Heating or
Electric Heat Only Option
Installed (cooling only
units)
nor nor = Reverse cycle heating
ELE = Electric heater installed
P-16 Fan Motor type selection
Shaded Pole or Split
Capacitor.
SC SP = Shaded pole fan motor
SC = Split capacitor fan motor
P-17 Reset Memorized
Programming Defaults
nor rSt = Reset defaults
nor = Normal
P-18 Reserved for Future
Option
––
P-19 Reserved for Future
Option
––
P-20 Filter Threshold
(x10 hours)
00 00 – 250
P-21 Current Filter Time
(x10 hours)
x10 Hours Using
Current Filter
P-22 Voltage Calibration (Volts) AC Voltage
Program
number
Description Default Range