P2 - Return Difference of Temperature of Hopper Cooling
Press “SETbuon to enter the P2 seng, press “UPor “DOWN”
to adjust the temperature from -9°C to 9°C, press “SETbuon
again to save the data and enter into the P3 seng.
P3 - Time Delay between Drive Motor & Compressor
Press “SET buon to enter the P3 seng, press “UP or
“DOWN” to adjust the me from 5 to 60 seconds, press “SET
buon again to save the data and enter into the P4 seng.
P4 - Compressor Restart Interval
Press “SET buon to enter the P4 seng, press “UP or
“DOWN” to adjust the me from 5 to 15 minutes, press “SET
buon again to save the data and enter into the P5 seng.
P5 - Time Delay Between Fan Motor & Drive Motor
Press “SETbuon to enter the P4 seng, press “UPor “DOWN”
to adjust the temperature from 5 to 15 minutes, press “SET
buon again to save the data and enter into the P1 seng.