[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-4 |
DOOCHPUMP
6.3 Drive Control Group
★To setup initial value according to drive capacity
☆To setup initial value with basis of Dooch induction motor
DISPLAY Name Range Factory Setting
Change
on
Operation
Ref.
Page
dr-01
dr-00
Command Input Location
CAN Comm. Speed 1~90 1
Setup
0~1 0 X
dr-02
Target Freq. Input
Method Setup
0~3 0 X
dr-03 Target Freq. Value Setup
Min Freq. (dr-42)~Max
Freq.
30.0 O
O
6-15
dr-10 Motor Capacity Selection 0.10~75.00[kW]
★
X
dr-11
No. of Motor Poles
Selection
1~2 1 X
dr-12 Rated Current of Motor 1.0~100.0[Arms]
☆
X
dr-13 Rated Rotations of Motor 1~9999[rpm]
☆
X
dr-14 Rated Voltage of Motor 200.0~500.0[Vrms]
☆
X
6-16
dr-15
Non-load Current of Motor
0.5~100.0[Arms]
☆
X
dr-16
Rated Slip Frequency of
Motor
0.10~10.00[Hz]
☆
X
dr-17
Rated Frequency of
Motor
0~1 1 X
dr-18 Efficiency of Motor 50~100[%]
☆
X
6-17
dr-20
Rotation Direction
Selection of Motor
0~1 0 X
dr-21
Stopping Method of
Motor
0~1 0 X
dr-22 Increase Time 1.0~600.0 3.0 O
dr-23 Decrease Time 1.0~600.0 6.0 O
6-18
dr-30
Motor Overload Trip
Selection
0~1 0 O
dr-31
Motor Overload Trip
Level
100~200[%] 120 O
dr-32
Motor Overload Trip
Time
5~200[sec] 60 O
dr-33 Stoll Prevention Setup 0~1 0 X
dr-34 Stoll Prevention Level 100~200[%] 150 X
dr-35
Motor Overheat
Selection
0~1 0 O
dr-36 Ground Detection 0~1 0 O
dr-37 No. of Restart after Trip 0~50 3 O
6-20
6-19