[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
Pr-73 Low Pressure Alarm Time
It sets maintaining time of low pressure alarm level to issue the low pressure alarm. That is, if the
current pressure decreases under the low pressure alarm level (Pr-71) and maintains its state for
a specified time, a low pressure alarm is displayed and operation stops.
Factory Setting Input Range Related Function
20[sec] 0~200[sec] Pr-71 Low Pressure Alarm Level
Pr-74 Low Water Level Alarm Time of Pressure Sensor
It sets maintaining time of alarm level to issue the low water level alarm.
That is, if the current pressure decreases under the low pressure alarm level (Pr-75) and
maintains its state for a specified time, an alarm is displayed and operation stops.
It is applied when low water level sensor setup (Pr-76) is released.
Factory Setting Input Range Related Function
Pr-75 Low Pressure Alarm Level
30[sec] 0~250[sec]
Pr-76
Low Pressure Alarm
Method Selection
Pr-75 Low Water Level Alarm Pressure Level
It is a pressure level to determine low water level when selecting software detection method from
Low Water Level Alarm Detection Method Selection (Pr-76).
Factory Setting Input Range Related Function
Pr-74
Low Water Level Alarm
Time of Pressure Sensor
0.3[bar] 0.0~1.0[bar]
Pr-76
Low Water Level Alarm
Method Selection
6-13 |
DOOCHPUMP
Pr-72 High Pressure Alarm Time
It sets maintaining time of high pressure alarm level to issue the high pressure alarm. That is, if
the current pressure increases above the high pressure alarm level (Pr-70) and maintains its
state for a specified time, a high pressure alarm is displayed and operation stops.
Factory Setting Input Range Related Function
5[sec] 0~100[sec] Pr-70
High Pressure Alarm
Level