[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-16 |
DOOCHPUMP
dr-03 Target Frequency Value Setup
When using as a fixed frequency, it is possible to set up target frequency value.
Target Frequency Input Method (dr-02) should be set with FND.
Factory Setting Input Range
30.0[Hz] Start Freq. (dr-42) ~Max Freq (dr-43)[Hz]
dr-10 Motor Capacity
It sets motor capacity.
It is set when pump drive is released from the factory. Setting value is for displaying.
It is used when the current pump drive checks the motor capacity being set.
Changing the setting does not have influence other parameters.
Factory Setting Input Range
Initial value is set upon drive capacity 0.10~ 75.00 [kW]
dr-11 Motor Pole Selection
It sets No. of motor poles.
It is set when pump drive is released from the factory.
Setup Data Functional Description
2 Pole Motor 1
4 Pole Motor 2
dr-12 Motor Rated Current
It sets up rated current (RMS) of the motor. It is based on the rated current indicated on the
nameplate of the motor.
It is applied to Stall Prevention Level, Slip Compensation Control and Overload Trip Level
Factory Setting Input Range
Initial value is set upon drive capacity 1.00 ~ 100.0 [Arms]
dr-02 Target Frequency Input Method Setup
It sets up target frequency input method of drive.
Setup Data Functional Description
0 (Factory Setting) Setup with own PID operation
Related Function
1
Setup when using fixed freq.
on the main body of FND
drive
dr-03
Target Freq. Value
Setup
Setup with external voltage V1(0~10V)2
Setup with external current I1(4~20mA)3