[CHAPTER 7 CAUSE OF FAULT AND REACTION]
7-4 |
DOOCHPUMP
Related Function Function Name Ref. Page
Pr-74 Pressure Sensor Low Level Trip Time
Pr-75 Pressure Sensor Low Level Trip Level
Pr-76 Low Level Detection Method Selection
6-13
Pr-77 Low Level Sensor Trip Time 6-14
Er-05 (Arm Short Trip-tASH )
Cause
In case acceleration/deceleration time is excessively short comparing to load inertia
Up/Down short circuit of IGBT
Output short circuit
Motor damage from fire and insulation defect
Reaction
Expand rising time (dr-22).
Check motor damage from fire and insulation fault.
Conduct test run by separating motor line from the drive. If the same alarm occurs, it would be
an up/down short circuit of IGBT. For that case, please contact A/S center.
Related Function Function Name Ref. Page
6-18Rising Timedr-22
Er-06 ( H/W Over Current Trip-tOC )
Cause
In case acceleration/deceleration time is excessively short comparing to load inertia
When drive restarts during free run of motor
Drive damage from fire
Reaction
Adjust the acceleration/deceleration time.
Check if the drive capacity is suitable for motor capacity.
Start the pump after the motor stopped.
Check load, motor, and output wiring.
If the same alarm occurs, please contact A/S center.
Related Function Function Name Ref. Page
dr-21 Motor Stopping Method
Rising Timedr-22
Falling Timedr-23
6-18