Liquid-Only Float Sensor
OPW P/N: 30-0230-S
Liquid-only Float Switch
Designed to detect the presence of fluid in the interstitial space of a
steel double-walled tank or a containment sump. The sensor, which
utilizes float technology, activates on the presence of water or fuel
and provides an alarm condition. An alarm condition will also occur if
the cable is broken.
Liquid-Only Float Sensor Installation
1. Check that the sump is dry.
2. Position the sensor approximately ½-inches (1.3 cm)
above the bottom of the sump/pan and secure sensor
wire to an existing pipe or bracket with a tie wrap.
3. Connect the sensor wires to the field wires in the junction
box using the supplied wire nuts.
4. Seal the electrical connections with the epoxy seal
packs.
Liquid-Only Float Sensor
Primary Use(s):
STP Sumps and Dispenser Pans
Alternate Use(s):
Use Steel Tank Interstitial
Detects:
Liquid
Operating Temperature:
-40°F to 158°F (-40°C to +70°C)
Dimensions:
Length: 3.5” (8.9 cm), Width: 1.43” (3.6 cm)
Cable Requirements:
Belden #88760 or Alpha #55371
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restrictions:
16 per I.S. barrier channel (64 per barrier)
Connections:
Red = Power, Black = Signal, Shield =
Ground
*NOTE: Maximum Wiring Length is the maximum length of cable to
be used to connect all sensors on an individual channel. This length
includes run of cable from I.S. Barrier to each sensor board in the
string.