EasyManua.ls Logo

Dranetz DranXperT - Specifications

Dranetz DranXperT
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50
SPECIFICATIONS*
GENERAL
Sampling Frequency: 32ksps (recorded and real-time meters),
128 samples per cycle (periodic waveform snapshots)
Sag/dip, swell trigger resolution: 1-cycle (uses IEC 61000-4-30
Class S methods)
Panel indicators: RGB LEDs for monitoring on/off, energy flow,
PQ event indication, battery charging/status, wiring status
Storage Capacity: 8GB
UL, CE
Voltage (3)
Range: 90 to 600VRMS CATIII
Accuracy: 90 VRMS to 600VRMS = ±0.1%, <90 VRMS = 0.5%
Connections: 4 safety banana voltage inputs – 3-phase voltage
and 1 neutral/reference
Current (4)
Input: 0.333 VRMS full scale, Connections: BNC
Accuracy: ±0.1% + probe
Frequency
Range: 50Hz = 45Hz to 55Hz, 60Hz = 55Hz to 65Hz
Accuracy: 50/60Hz: ±0.001Hz
POWER QUALITY
Sag/dip, swell trigger threshold resolution: 1-cycle
Vthd: ±5% for V 10% Vnom
Ithd: ±5% for I 10% Inom + probe error
ENERGY PARAMETERS (probe dependent)
(True/Active) Energy (P): 0.1%
Reactive Energy (Q): 0.1%
Apparent Energy (S): 0.1%
Fundamental Active Energy(P): 0.2%
Fundamental Reactive Energy(Q): 0.2%
Fundamental Apparent Energy (S): 0.2%
Demand: 0.2%