SIA Format (Level 2—Hardcoded)
This format will send the account code along with its
data transmission. At the receiver, the transmission
would look similar to this example:
N Ri01 BA 01
N = New Event
Ri01 = Partition / Area Identifier
BA = Burglary Alarm
01 = Zone 1
Contact ID
The first digit (in parentheses) will automatically be sent by
the control panel. The last two digits are programmed to
indicate specific information about the signal.
For example, if zone 1 is an entry/exit point, the alarm
reporting code could be programmed as [34]. The central
station would receive the following:
*BURG - ENTRY/EXIT - 1
In the above example, the “1” indicates which zone went
into alarm.
42
Reporting Codes
APPENDIXV A
Section
#
Reporting Code Code Sent When... Dialer
Direction*
Auto-
matic
Contact
ID
SIA Auto
Rep Codes**
[320-323]
Zone Alarms zone goes into alarm A/R (1) 3A See
Ta b l e B - 1
[324-327]
Zone Restorals zone in alarm is restored A/R (1) 3A
[328]
Duress Alarm duress code entered at keypad A/R (1) 21 HA-00
[328]
Opening After
Alarm
system disarmed with alarm in memory A/R (4) A6 OR-00
[328]
Recent Closing alarm occurs within two minutes of system arming A/R (4) 59 CR-00
[328]
Zone Expander
Supervisory
Alarm/Rest.
panel loses/restores supervisory transmission over
the Keybus from zone expansion modules or
keypads with zone inputs
A/R (1) 43 UA-00/UH-00
[328]
Cross Zone (Police
Code) Alarm
two zones on the same partition go into alarm
during any given armed-to-armed period (incl. 24-
hr zones)
A/R (1) 4A BV-00
[329]
[F] Key Alarm/Rest. Keypad fire alarm (alarm and restoral reporting
codes sent together)
A/R (1) 15 FA-00/FH-00
[329]
[A] Key Alarm/Rest. Keypad auxiliary alarm (alarm and restoral
reporting codes sent together)
A/R (1) AA MA-00/MH-00
[329]
[P] Key Alarm/Rest. Keypad panic alarm (alarm and restoral reporting
codes sent together)
A/R (1) 2A PA-00/PH-00
[329]
PGM2 Alarm/Rest. Output Option #23/24: a panic button wired to
PGM2 is pressed/access code is entered
A/R (1) 4A UA-99/UH-99
Output Option #04: a 2-wire smoke detector wired
to PGM2 goes into alarm/alarm is cleared
A/R (1) 11 FA-99/FH-99
[330-]
[337]
Zone Tamper/Rest. zone exhibits a tamper condition/tamper condition
restored
T/R (1) 44 TA-ZZ/TR-ZZ
[338]
General System
Tamper/Rest.
enrolled module with tamper inputs has a tamper
alarm/all module tampers restored
T/R (1) 45 TA-00/TR-00
[338]
Keypad Lockout max. number of incorrect access codes has been
entered at a keypad
T/R (4) 21 JA-00
[339-343]
Closings system armed (user 01-34, 40-42 indicated) O/C (4) A2 CL-UU
[343]
Partial Closing one or more zones are manually bypassed when
system armed (or Auto-armed)
O/C (4) 7A CG-00
[343]
Special Closing Closing (arming) using one of the following
methods: Quick Arm, Auto-arm, keyswitch,
wireless key, function key, maintenance code, DLS
O/C (4) AA CL-00
Table A-1: PC5015 Reporting Codes