OPERATION
9
POWERCORD
Using Extension Cords
Westinghouse Portable Power assumes no responsibility for the content within this table. The use of this table is the
responsibility of the user only. This table is intended for reference only. The results produced by using this table are
not guaranteed to be correct or applicable in all situations as the type and construction of cords are highly variable.
Always check with local regulations and a licensed electrician prior to installing or connecting an electrical appliance
INVERTER PARALLELING OPERATION
INVERTER PARALLELING OPERATION
It is possible to connect two D4000iS generators to
each other, using a parallel cable kit, to increase
available power output.
Connect PARALLEL OPERATION CABLES to two
D4000iS generators according to the instructions
provided with the cable kit.
Make sure the Economy switch is in the same
position on both generators.
All electronic devices should be turned “OFF” and
disconnected from generators prior to starting
generator engines.
Start generator engines. Make sure the green output
indicator light comes on for each generator.
When engines have stabilized, plug in electronic
device to AC receptacle and turn on first load.
Allow generator output to stabilize (engine and at-
tached devices run evenly) before plugging in the
next load.
Maximum Power in Parallel Operation: 8.0kVA
Rated Power in Parallel Operation: 7.0kVA
Limit operation time to 3 seconds for load requiring maxi-
mum output. For continuous operation, do not exceed the
rated output.
Note: It is strongly recommended to plug in devices
with the largest output first and the smallest output last to
help prevent overloading the generator.
DANGER
Never connect
the
paralleling
cord
to the inverters with the inverters run-
ning. The inverters must not be
run-
ning and both the paralleling cord
switches must be off when connecting
the cords.
WARNING
Do not attempt to parallel the inverter
with any other manufacturers’
invert-
ers. Do not use the paralleling cord for
any application other than inverter
paralleling. Do not
use this
cord on ot-
her manufacturers’ inverters.
Always ensure that both ends of
the paralleling cord are switched off
before connecting the inverters.