Do you have a question about the Dungs DMV Series and is the answer not in the manual?
Installation and maintenance must be done by trained specialists. Never work with gas pressure or power applied, or near an open flame.
Read instructions before use and keep them safe. Failure to follow may cause injury or property damage.
Adjustments must follow appliance/boiler manufacturer instructions. Verify application suitability with product ratings.
Disconnect power, close shut-off valve, remove electrical connector, and disassemble brake unit/knob and solenoid.
Verify replacement coil, install it, replace washer, check/remount brake unit/knob, and secure screws.
Perform external leakage test with gas pressure and power applied. Conduct a complete function test for valve operation.
Installation and maintenance must be done by trained specialists. Never work with gas pressure or power applied, or near an open flame.
Read instructions before use and keep them safe. Failure to follow may cause injury or property damage.
Adjustments must follow appliance/boiler manufacturer instructions. Verify application suitability with product ratings.
Disconnect power, close shut-off valve, remove electrical connector, and disassemble brake unit/knob and solenoid.
Verify replacement coil, install it, replace washer, check/remount brake unit/knob, and secure screws.
Perform external leakage test with gas pressure and power applied. Conduct a complete function test for valve operation.
This document provides installation instructions for the DMV/6x2 Series Coil Replacement for Dungs Combustion Controls. It is a critical guide for ensuring the safe and proper maintenance of the device. The manual emphasizes the importance of qualified personnel for all installation and maintenance procedures, highlighting the potential for personal injury or property damage if instructions are not followed.
The DMV/6x2 Series Coil Replacement is designed to replace the solenoid coil on Dungs DMV/6x2 series valves, which are integral components in combustion control systems. These valves typically regulate gas flow, and the solenoid coil is responsible for their electrical actuation, allowing them to open and close as required by the control system. The replacement process involves disconnecting power, removing the old coil, and installing a new one, ensuring that the valve continues to function correctly and safely. The instructions also cover the inspection and testing of related components, such as the hydraulic brake unit or black adjustment knob, and the associated O-rings, to maintain the overall integrity and leak-tightness of the valve assembly. Proper coil replacement is essential for the reliable operation of the combustion system, preventing gas leaks and ensuring efficient fuel delivery.
The installation instructions are structured to guide users through a systematic replacement process. Key usage features include:
The manual outlines several features that are crucial for effective maintenance of the DMV/6x2 series valves:
| Closing Time | < 1 s |
|---|---|
| Opening Time | < 1 s |
| Application | Gas burner control |
| Max. Operating Pressure | 500 mbar |
| Valve Class | A |
| Approvals | EN 161 |
| Operating Temperature | -20°C to +60°C |
Loading...