Property Default Values User
Writable
Data Type
Object Identier
Object Name
Object Type
Status Flags
Event State
Reliability
Out Of Service
Network Type
Protocol Level
Network Number
Network Number
Quality
Changes Pending
MAC Address
APDU Length
Link Speed
Link Speeds
Link Speed
Autonegotiate
Max Master
Max Info Frames
NP1
“MS/TP”
Network Port
{0,0,0,0}
Normal
No Fault Detected
FALSE
MSTP
BACnetApp
0
Unknown
FALSE
127
480
**current baud rate**
{9600,19200,38400,57600,768
00,115200}
TRUE
127
1
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Object Identier
Character String
Object Type
Status Flags
Event State
Reliability
Boolean
Network Type
Protocol Level
Unsigned16
Network Number
Quality
Boolean
Octet String
Unsigned
Real
BACnetArray of
Real
Boolean
Unsigned8
Unsigned8
Property Default Values User
Writable
Data Type
Object Identier
Object Name
Object Type
Present Value
Max Present Value
Min Present Value
Status Flags
Event State
Reliability
Out Of Service
Units
AV1
“Humidity Offset %RH”
Analog Value
0
3.5
-3.5
{0,0,0,0}
Normal
No Fault Detected
FALSE
percent-relative-humidity
No
No
No
Yes
No
No
No
No
No
Yes
No
Object Identier
Character String
Object Type
Real
Real
Real
Status Flags
Event State
Reliability
Boolean
Engineering
Units
Property Default Values User
Writable
Data Type
Object Identier
Object Name
Object Type
Present Value
Max Present Value
Min Present Value
Status Flags
Event State
Reliability
Out Of Service
Units
AV2
“Temperature Offset deg F”
Analog Value
0
-5
5
{0,0,0,0}
Normal
No Fault Detected
FALSE
degrees-fahrenheit
No
No
No
Yes
No
No
No
No
No
Yes
No
Object Identier
Character String
Object Type
Real
Real
Real
Status Flags
Event State
Reliability
Boolean
Engineering
Units
Property Default Values User
Writable
Data Type
Object Identier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out Of Service
Number Of State
State Text
MSV1
“Temperature Display Unit”
Multi-State Value
1
{0,0,0,0}
Normal
No Fault Detected
FALSE
2
””Degrees Fahrenheit”,
”Degrees Celsius”
No
No
No
Yes
No
No
No
Yes
No
No
Object Identier
Character String
Object Type
Real
Status Flags
Event State
Reliability
Boolean
Unsigned
BACnetArray of
CharacterString
Property Default Values User
Writable
Data Type
Object Identier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out Of Service
Number Of State
State Text
MSV2
“Humidity Display
Measurement”
Multi-State Value
3
{0,0,0,0}
Normal
No Fault Detected
FALSE
7
“Due Point (degrees F)”,
“Due Point (degrees C)”,
“Relative Humidity (%RH)”,
“Enthalpy (BTU/lb)”,
“Absolute Humidity (lb/MMCF)”,
“Enthalpy (kJ/kg)”,
“Absolute Humidity (g/m^3)”
No
No
No
Yes
No
No
No
Yes
No
No
Object Identier
Character String
Object Type
Real
Status Flags
Event State
Reliability
Boolean
Unsigned
BACnetArray of
CharacterString
III. BACnet ANALOG VALUE OBJECTS
IV. BACnet MULTI-STATE VALUE OBJECTS
V. BACnet NETWORK PORT OBJECTS
MAINTENANCE/REPAIR
Upon nal installation of the Series RHPX, no routine maintenance is required.
The Series RHPX is not eld serviceable and is not possible to repair the unit.
Field repair should not be attempted and may void warranty.
Do not dispose of as unsorted domestic or municipal waste. Consult
retailer or local authorities for recycling information.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website.
Contact customer service to receive a Return Materials Authorization (RMA)
number before shipping the product back for repair. Be sure to include a brief
description of the problem plus any additional application notes.