7
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons   MN132021EN   November 2016
Probe Adapter Reassembly
Step 12
Holding the square portion of the cable housing, complete 
fuse assembly using the supplied 3/16" hex wrench. Tighten 
until fuse bottoms and the hex wrench twists.
Confirm check dimension shown in illustration above. 
Position the long end of the hex wrench on the cable 
housing nosepiece, verify that the top of the fuse end cap is 
equal to or below indicator notch on the hex wrench.
 
Check Dimension
Use the Hex 
Wrench notch to 
measure proper 
depth.
Indicator Notch
Indicator Notch
Step 13
Install probe adapter on unthreaded stud. Probe adapter 
should rest flush on top of fuse end cap.
 
Probe Adapter
Probe Adapter Seated 
Flush On Top of Fuse 
End Cap
Fuse End Cap