7
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons MN132021EN November 2016
Probe Adapter Reassembly
Step 12
Holding the square portion of the cable housing, complete
fuse assembly using the supplied 3/16" hex wrench. Tighten
until fuse bottoms and the hex wrench twists.
Confirm check dimension shown in illustration above.
Position the long end of the hex wrench on the cable
housing nosepiece, verify that the top of the fuse end cap is
equal to or below indicator notch on the hex wrench.
Check Dimension
Use the Hex
Wrench notch to
measure proper
depth.
Indicator Notch
Indicator Notch
Step 13
Install probe adapter on unthreaded stud. Probe adapter
should rest flush on top of fuse end cap.
Probe Adapter
Probe Adapter Seated
Flush On Top of Fuse
End Cap
Fuse End Cap