3
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons   MN132021EN   November 2016
Probe and Elbow Housing Disassembly
Step 3
After a visible ground is achieved on both sides of the 
fuse, remove the Fused Loadbreak Elbow Connector from 
feedthru device.
Step 4
Install supplied wire probe wrench into wrench hole of 
loadbreak probe. Turning counterclockwise, unthread and 
remove loadbreak probe from fused loadbreak elbow.
Remove Loadbreak Probe
Wire 
Probe 
Wrench
Drain Wires
Turn Counterclockwise 
to loosen
Step 5
Detach drain-wire lead from the drain-wire eye of the 
elbow housing. At the overlap of elbow housing and cable 
housing, insert supplied bleeder strap approx. 1/2" (13 
mm) under lip of elbow housing. Slide strap around the 
entire circumference of fused loadbreak elbow to vent 
the interfaces. Leave the bleeder strap inserted between 
housings.
Cable Housing
Bleeder Strap
Elbow Housing
Probe Removed
Elbow and Cable Housing Overlap