2
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons   MN132021EN   November 2016
Fuse Replacement Procedures
Complete current-limiting replacement fuse includes:
 
Current-Limiting Fuse
 
Two (2) Spare Set Screws
 
Bleeder Strap
 
Two (2) Probe Installation Tools
 
One (1) 1/8" Hex Wrench
 
Two (2) 3/16" Hex Wrenches
 
Silicone Lubricant
 
Installation Instruction Sheet
  DANGER
Hazardous Voltage. Both sides of the fused loadbreak 
elbow must be disconnected and grounded prior to 
any hands-on installation or maintenance. Failure to 
comply will result in death or severe personal injury and 
equipment damage.
   WARNING
The operator should always use personal protective 
equipment (insulated gloves, clampstick and eye 
protection) whenever operating the fused loadbreak 
elbow. The operator should always be in the best 
possible operating position, providing firm footing 
and enabling a secure grasp of the clampstick, while 
maintaining positive control of the elbow before, during 
and immediately after operation. If there is any question 
regarding the operator’s operating position, de-energize 
the elbow before operation. The operator should not be 
looking directly at the connector during the moment 
of circuit interruption or connection. Failure to comply 
could result in death or serious injury.
   WARNING
Capacitive Test Point Operating Instructions: Use only 
voltage indicating instruments specifically designed for 
test points. Use of conventional voltage sensing devices 
may provide false “No Voltage” indications. 
The test point must be dry and free of contaminants 
when checking for voltage. After indication is taken: 
clean, dry, and lubricate the test point cap with silicone 
grease and assemble to the test point.  
Always consider the termination to be energized until 
the test point “No Voltage” indication is confirmed by 
other means. Failure to comply could result in death or 
severe personal injury.
Step 1
Voltage Test  Operation
The Fused Loadbreak Elbow Connector is equipped with 
two integral capacitive test points that can be used to 
establish whether or not the fuse has interrupted the tap 
circuit. The test point on the source side of an open fuse 
will indicate a voltage while the test point on the tap side 
of the fuse will indicate no voltage. Both test points will 
indicate a voltage if the fuse has not operated.
Step 2 
Establish visible break and visible ground
Using a clampstick, isolate fuse by disconnecting the 
Fused Loadbreak Elbow Connector from the apparatus 
bushing and parking the Fused Loadbreak Elbow Connector 
on an appropriate feedthru device. Install an insulated 
protective cap on the apparatus bushing. Isolate the Fused 
Loadbreak Elbow Connector on the tap-end of the fuse by 
disconnecting and placing the tap-end cable termination 
on an appropriate feedthru device. Install an insulated 
protective cap on the tap-end apparatus bushing. Then 
create a visibly traceable ground on both sides of the fuse.