4
200 A Fused Loadbreak Elbow Connector Replacement Fuse
InstallatIon InstructIons MN132021EN November 2016
Fuse Disassembly
Step 6
Gripping the square portion of the cable housing, and
keeping the cable housing stationary, apply a twist-and-pull
motion to the elbow housing to separate it from the cable
housing.
ote:N A screwdriver through the pulling eye on top of the
elbow will aid in twisting and pulling to separate.
Discard bleeder strap after housings are separated.
Elbow Housing
Upper
Pulling
Eye
Cable
Housing
Grip While
Separating
Facing
Outward
Separate
Step 7
Using the supplied 1/8" hex wrench, unthread the two set
screws from the probe adapter.
1/8" Hex Wrench