17
Three phase system
Recommended circuit breaker and contactor current specifications:
UPS
MBP model
Input mode
Breaker
Contactor
15KVA
MBP20K
MBP20KPDU
1 phase main input
D type 125A
≥125A
3 phase main input
D type 63A
63A
1 phase bypass input
D type 100A
≥100A
3 phase bypass input
D type 40A
≥40A
1 phase output
D type 100A
≥100A
3 phase output
D type 40A
≥40A
MBP20KPARA
1 phase main input
D type 230A
230A
3 phase main input
D type 80A
80A
1 phase bypass input
D type 160A
≥160A
3 phase bypass input
D type 63A
63A
1 phase output
D type 160A
≥160A
3 phase output
D type 63A
63A
20KVA
MBP20K
MBP20KPDU
1 phase main input
D type 160A
≥160A
3 phase main input
D type 63A
≥63A
1 phase bypass input
D type 125A
≥125A
3 phase bypass input
D type 63A
63A
1 phase output
D type 125A
≥125A
3 phase output
D type 63A
63A
MBP20KPARA
1 phase main input
D type 300A
300A
3 phase main input
D type 100A
100A

Related product manuals