18
1 phase bypass input
D type 230A
230A
3 phase bypass input
D type 80A
80A
1 phase output
D type 230A
230A
3 phase output
D type 80A
80A
Cable and connector
The cable’s conductor size should be selected based on the size of the UPS power module.
Refer to the following two tables for the cross-sectional dimensions in mm². Each for 15kvA
and 20kVA UPS respectively:
15kVA UPS
MBP Model
Input/
Output
Mode
Input
Output
Main input
Bypass input
Ground wire
L wire
N wire
L wire
N wire
L wire
N wire
Ground
wire
MBP20K
MBP20KPDU
3-1
6
6
16
16
16
16
16
16
3-3
6
6
6
6
6
6
6
6
1-1
35
35
16
16
35
16
16
16
1-3
35
35
6
6
35
6
6
6
MBP20KPARA
3-1
16
16
50
50
50
50
50
50
3-3
16
16
10
10
16
10
10
10
1-1
95
95
50
50
95
50
50
50
1-3
95
95
10
10
95
10
10
10

Related product manuals