20kVA UPS
Notes
1. For single input connection, please select the larger conductor size cross-section.
2. UPS output cable length is recommended not to exceed 10m.
Please refer to the following table for conductor’s terminal selection:
20KVA UPS
MBP Model
Input/
Output
Mode
Input
Output
Main input
Bypass input
Ground wire
L wire
N wire
L wire
N wire
L wire
N wire
Ground
wire
MBP20K
MBP20KPDU
3-1
10
10
25
25
25
25
25
25
3-3
10
10
10
10
10
10
10
10
1-1
50
50
25
25
50
25
25
25
1-3
50
50
10
10
50
10
10
10
MBP20KPARA
3-1
25
25
70
70
70
70
70
70
3-3
25
25
16
16
25
16
16
16
1-1
120
120
70
70
120
70
70
70
1-3
120
120
16
16
120
16
16
16
Conductor cross-section (Unit:mm²)
Ring terminal type
6
DRNB6-6
10
DRNB6-10
16
DRNB8-16
25
DRNB8-25
35
DRNB8-35
50
DRNB8-50
70
DRNB8-70
95
DRNB8-95
120
DRNB8-120