EasyManua.ls Logo

Eaton 9SX 15K Series - Normal Mode to Maintenance Bypass Mode

Eaton 9SX 15K Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
4.2 Normal mode to maintenance bypass mode
Remove plastic-panel:
Loosen the plastic panel screws of the MBP and remove the plastic panel as shown below.
Rotate the ‘Maintenance Bypass Switch’:
1. Remove the protective panel of 'Maintenance Bypass Switch'.
2. At this point, the UPS will transfer to internal bypass automatically (given MBP
detection cables are connected properly).
3. Rotate the handle of the Maintenance Bypass Switch to the ‘MAINTENANCE’
position.
Open the ‘Input switch’:
1. Set the UPS to standby mode from the LED screen control
2. Open all the ‘Input switch’ by pushing the swith levers downwards on the front panel
of the MBP to the ‘OFF’ position
3. The recommended operation sequence is: UPS input switch UPS bypass switch
UPS Neutral switch.