27
3.1.5 Mode 1-1(single source)
1. Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the ‘AC input terminal N/N’ with ‘busbar #1’, then connect the AC cable
(N) to it
III. Bridge the ‘AC input terminals mL1/bL1/mL2/bL2/mL3/bL3 with ‘busbar #6’, then
connect the AC cable (L) to it
2. Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the ‘AC segment terminal N/N’ with ‘busbar #1’, then connect the AC
cable (N) to it
III. Bridge the ‘AC segment terminals L1/L2/L3’ with ‘busbar #3’, then connect the
AC cable (L) to it
3. Connection to the UPS:
I. Remove all the busbars of the UPS