48
1. Input:
I. Connect the main-ground cable (PE) to the chassis
II. Bridge the ‘AC input terminal N/N/N’ with ‘busbar #9, then connect the AC main
source cable (N) and bypass source cable (N) to it
III. Bridge the ‘AC input terminal mL1/mL2/mL3’ with ‘busbar #12’, then connect the
main source cable (L) to it
IV. Connect the ‘AC input terminal bL1’ to the bypass source cable (L)
2. Output:
I. Connect the ground cable (PE) to the chassis
II. Bridge the ‘AC segment terminal N/N/N’ with ‘busbar #3, then connect the AC
cable (N) to it
III. Connect the ‘AC segment terminal L1/L2/L3’ to AC cable (L1/L2/L3)
3. Connecting to UPS 1 and UPS 2:
III. Remove all busbars of the UPS
IV. Connect UPS 1 and UPS 2 to the MBP with ‘Cable to UPS 1’ and Cable to UPS
2’ included in the MBP’s accessory
Note:
Bypass is not available in this mode. Please use with caution.