29
4.1.5. Mode 1-1 (single source)
1. Input: connect the main ground cable (PE) to the chassis first
2. Bridge the ‘UPS input terminal N/N’ with ‘busbar #1’, then connect the
AC cable(N)
3. Fix the jumper cables’ to the ‘UPS input terminal L1/L2/L3’ and ‘busbar
#2’, then bridge the ‘UPS bypass terminal L1/L2/L3’ with this ‘busbar
#2’ and connect the AC cable (L)
4. Output: connect the ground cable (PE) to the chassis first;
5. Bridge the ‘UPS output terminal N/Nwith busbar #1’, then connect
the AC cable (N)
6. Bridge the ‘UPS output terminal L1/L2/L3’ with ‘busbar #2’, then
connect the AC cable (L)
For 1 Phase input connection, if set to CVCF (Frequency Converter) mode,
the UPS needs to be derated to 60% of its rated capacity.