EasyManua.ls Logo

Eaton 9SX 20KPM Series - wiring

Eaton 9SX 20KPM Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
5.2 wiring
Cable-selection table for the paralleled system AC IN and AC OUT :
Paralleled system installed by 15KVA UPS (conductor cross-section, unit: mm²)
UPS
number
Mode
Main
input
Bypass
input
Ground wire
Output
Battery wire
Battery ground
L wire
N wire
L wire
N wire
L wire
N wire
Ground
2 UPS
3-1
16
16
50
50
50
50
50
50
25
25
3-3
16
16
10
10
16
10
10
10
25
25
1-1
95
95
50
50
95
50
50
50
25
25
1:3
95
95
10
10
95
10
10
10
25
25
3 UPS
3-1
35
35
95
95
95
95
95
95
50
50
3-3
35
35
16
16
35
16
16
16
50
50
1-1
185
185
95
95
185
95
95
95
50
50
1-3
185
185
16
16
185
16
16
16
50
50

Related product manuals