36
should be less than 20%.
If the distance between the load and the paralleled system is greater than
20 meters, the length difference between the UPS-to-UPS interconnecting
lines should be less than 5%.
Professional installation is required, please deploy the paralleled system in
the restricted area!
5.1 Paralleled UPS installation
In the paralleled system, the installation of the UPS modules are the same as single
UPS. Please refer to Chapter 3.
Note:
If used, the 1 + 1 parallel MBPshould be placed on top of the paralleled UPSs for
rack mounting, or on the left for a tower installation (as shown below):
Rack mount for parallel system Tower mount for parallel system