Note:
1. For single input connection, please select the larger conductor size cross-section.
2. If the load in a 3-phase output mode is unbalanced, the L wire of the bypass and
output may exceed the rated current by 1.732 times. . The corresponding
protection device and wiring cable must be determined according to the
standards of the region and the actual situation of the user.
5.2.1 Basic parallel UPS wiring
Complete the AC connection for the parallel system per the previous section.
Remove the protective cover of the parallel ports, then connect the ‘parallel cable’
(25-pin included as an accessory) to each UPS’ parallel port. The connection
should be a closed loop (as shown below):