58
mode without interruption to the output.
In battery mode, the buzzer will beep once every 4 seconds to indicate that
batteries are being discharged. To disable this alarm, see section 7.3.4
Setting General
Since utility power is not present, the input out of tolerance alarm will
appear on the LCD screen.
7.4.2 UPS Shutdown
Shutting down the UPS with in Online mode:
Press and hold the On/Off button for more than 3s until the LCD shows a
confirm shutdown page.
Tap on Confirm and wait for the UPS to shut down.
After the shut down, the UPS will still be on bypass mode.
Disconnect the utility power to shut down the load.
Shutting down the UPS in battery mode:
Press and hold the On/Off button for more than 3s until the LCD shows a
confirm shutdown page.Tap on Confirm and wait for the UPS to shut down.
The load will be dropped, and the UPS will go to standby mode, before
automatically powering down after a few seconds.
7.4.3 UPS function
Working modes
Mode
Break time
Output frequency
PF correction
Online mode
0ms
Synchronised with the
input within range
Yes
High efficiency
mode
10ms
Synchronised with the
input
No
ESS mode
2ms
Synchronised with the
input
No
CVCF mode*
0ms
Fixed 50Hz/60Hz
Yes
*NOTE: In CVCF mode, if UPS is connected to a single-phase input, the UPS
rating needs to be derated to 60% of its rated capacity.
Automatic Restart
After the battery is depleted and utility power is restored, the UPS will enter
the bypass mode and charge the batteries. If automatic restart is enabled, and