Page 55
614-20306-00 - 9SX 0-6 KVA EMEA_EN
8. Specifications
Table 7. Electrical output connection
Part Number Output connection Output cables
9SX700I (3) IEC10A
(2) IEC10A Group 1
(1) IEC10A Group 2
(2) IEC10A 2 meters
9SX1000I
9SX1000IM
9SX1000IR
9SX1500I
9SX1500IR
9SX2000I (4) IEC10A
(2) IEC10A Group 1
(2) IEC10A Group 2
9SX2000IR
9SX3000I (4) IEC10A + (1) IEC16A
(2) IEC10A Group 1
(2) IEC10A Group 2
9SX3000IM
9SX3000IR
9SX5KI NA NA
9SX6KI NA NA
Table 8. Environmental and safety
Certifications IEC/EN 62040-1
IEC/EN 62040-2: Cat. C1
IEC/EN 62040-3
UL1778 5
th
edition (for 0-3KVA)
CSA 22.2 (for 0-3KVA)
EMC (Emissions)* CISPR22 Class B
FCC part 15 Class B / ICES-003 (for 0-3KVA)
EMC (Immunity) IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
* for output cable < 10m.
Agency markings CE / cULus (for 0-3KVA) / EAC / RCM / KC / Energy Star
Operating temperature 0 to 40 °C (32 to 104 °F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 0 to 40 °C (32 to 104 °F) with batteries
-25 to 55 °C (-13 to 130 °F) without batteries
Transit temperature -25 to 55 °C (-13 to 130 °F)
Relative humidity 0 to 96% no condensing
Operating altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for 35 °C (95 °F)
room temperature
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 50 dBA at 1 meter typical