87
Mode 1-1(dual source)
1. Input: connect mian-ground cable (PE) to chassis first;
short UPS input terminal N/N’ with ‘busbar #1’, then connect AC main
source cable(N) and bypass source cable(N) by back to back mounted;
short ‘UPS input terminal L1/L2/L3 with ‘busbar #2’, then connect main
source cable(L).
short ‘UPS bypass terminal L1/L2/L3’ with busbar #2’, then connect
bypass source cable(L).
2. Output: connect ground cable (PE) to chassis first;
short ‘UPS output terminal N/N’ with ‘busbar #1’, then connect AC
cable(N);
short UPS output terminal L1/L2/L3’ with ‘busbar #2’, then connect AC
cable(L)