88
Mode 1-3(single source)
1. Input: connect mian-ground cable (PE) to chassis first;
short ‘UPS input terminal N/N’ with ‘busbar #1’, then connect AC cable(N);
Fix ‘jumper cable’ to ‘busbar #2’, then short ‘UPS input terminal L1/L2/L3’
with this ‘busbar #2’ and connect AC cable(L), connect this ‘jumper cable’
to ‘UPS bypass terminal L1’ finally.
2. Output: connect ground cable (PE) to chassis first;
short ‘UPS output terminal N/N’ with ‘busbar #1’, then connect AC
cable(N);
connect ‘UPS output terminal L1/L2/L3’ to AC cable(L1/L2/L3).