EasyManua.ls Logo

Eaton 9SX Series - Page 94

Eaton 9SX Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88
Mode 1-3(single source)
1. Input: connect mian-ground cable (PE) to chassis first;
short ‘UPS input terminal N/N’ with ‘busbar #1’, then connect AC cable(N);
Fix ‘jumper cable’ to ‘busbar #2’, then short ‘UPS input terminal L1/L2/L3’
with this ‘busbar #2’ and connect AC cable(L), connect this ‘jumper cable’
to ‘UPS bypass terminal L1’ finally.
2. Output: connect ground cable (PE) to chassis first;
short ‘UPS output terminal N/N’ with ‘busbar #1’, then connect AC
cable(N);
connect ‘UPS output terminal L1/L2/L3’ to AC cable(L1/L2/L3).

Other manuals for Eaton 9SX Series

Related product manuals