1.5 .4 How the ATC-9 0 0 evaluates Closed or In-phase transitions
The controller software will confirm that the Closed Transition 
(CT) or In-phase transition is enabled through the set-points.  
When Source 1 and Source 2 are both Available within voltage 
and frequency set point tolerances:
• If S1 and S2 set points (UV/OV, UF/OF) are identical, there can 
be a difference in voltage and/or frequency when transition 
occurs.  Also, if there is a difference in setpoints, the actual 
voltage and/or frequency may be identical when the transition 
occurs.
• It confirms that sources are within Closed or In-phase transi-
tions set point tolerances when:
– Voltage difference for Closed = +/- 1 to 5%, 
– There is no voltage difference setpoint for in-phase.  As 
long as both voltages are with in voltage limits any differ-
ence in acceptable
– Freq. difference = +/- 0 to 0.3 Hz for closed
– Freq. difference = +/- 0 to 3 Hz for In-phase 
– Phase Angle closed or in-phase, when the number of Gen-
erators = 0, the phase angle difference is fixed at +/- 8 
degrees 
– Phase Angle closed or in-phase, when the number of Gen-
erators = 1 or 2, the phase angle difference is fixed at +/- 
5 degrees 
• The controller attempts to close or in-phase transition until the 
Sync Timer's set point (1 to 60 min) expires. 
Synchroscope Data for In-phase & Closed Transitions
The synchroscope is a useful tool for sync type transitions. When 
the controller is waiting for synchronization for either In-phase or 
Closed transitions, there is a timer countdown and the display will 
show the following:
Phase Angle  xxx degrees          Sync Timer   hh:mm:ss
The phase angle is between 0 and 365 degrees. On each closed 
transition type switch, there is a parallel limit timer that either 
opens the breaker or sends a close to user terminal blocks (con-
tactor types) that can be used to open breakers upstream, if the 
overlap time is greater than what was set by the user.  Please 
check the switch instruction booklet for more information. 
Section 2: Hardware Description
2.1 General
The purpose of this section is to familiarize the reader with ATC-
900 hardware, its nomenclature, and to list the unit’s specifica-
tions. The information presented is divided into the following four 
parts:
• Operator Panel; 
• Rear Access Area; 
• External Hardware; and
• Specification Summary.
2.2 Operator Panel
The operator panel, which is normally accessible from the outside 
of a panel or door, provides a means for:
• Being alerted to specific conditions; 
• Receiving functional help; 
• Programming; and
• Parameter Monitoring/Selection/Metering.
LEDs, a display, pushbuttons, and a mimic bus make up the front 
accessible operator panel (Figure 1).
The Color high resolution TFT LCD is used to display all ATC-900 
monitored parameters, setpoints and messages in an easy to read 
format. The display is approximately 2.25" x 4" (57.15mm x 
101.6mm). The TFT display is not a touch screen.
The front operator panel supports seven long-life extended tem-
perature membrane pushbuttons.
2.3 Rear Access Area
The rear access area of the ATC-900 is normally accessible from 
the rear of an open switch panel door (Figure 2).
All wiring connections to the ATC-900 are made at the rear of the 
chassis. For the sake of uniform identification, the frame of refer-
ence when discussing the rear access area is facing the back of 
the ATC-900 with the panel door open. Keeping safety in mind, 
programming and downloading setpoints, history, and events can 
all be accomplished with the front door closed. A USB connector 
with a cover is brought out from the back of the controller to the 
front of the door on the switch using the device panel.
2.3 .1 Connections on Chassis
The rear of the chassis provides self locking female connectors. 
See Figure 2 for connections for the left, right, and top of the 
ATC-900. See Section 4 for more information on input functional-
ity. The part numbers of the connectors are shown below:
Connector Designation
J1  Source 1 Sense Lines
J2  Source 2 Sense Lines
J3  Load Sense Lines
J4 Programmable Outputs (4) & Source Available Form C 
J5 RS-232 (Factory Use)
J6 Transfer Control and Aux Inputs
J7 Control Power from Sources 1 and 2 (see note below)
J8 USB Stick (thumb) Drive Connection (connector brought out to 
front door panel)
J9 Programmable Inputs (4)
J11 I/O Module Interface
J12 Modbus 485 (User)
J13  RS-422 (Future Use)
J14 DCT Module Interface
Note: Controller power for Source 1, J7-1,2 must be electrically isolated 
from control power for Source 2, J7-3,4.