EasyManua.ls Logo

Eaton CPX9000 - Table 3-5: Analog Value Object

Eaton CPX9000
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BACnet MS/TP Option Board OPTCJ for 9000X Drives User Manual
3-6 For more information visit: www.EatonElectrical.com
MN04012006E
August 2006
Table 3-4: Binary Value Object (Continued)
Note: For Present Value Access Types, R = Read-only, W = Writable, C = Commandable.
Commandable values support priority arrays and relinquish defaults.
Table 3-5: Analog Value Object
Instance
ID Object Name Description Inactive/Active
Present Value
Access Type
BV24 FBFixedControlWord
Bit_9
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV25 FBFixedControlWord
Bit_10
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV26 FBFixedControlWord
Bit_11
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV27 FBFixedControlWord
Bit_12
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV28 FBFixedControlWord
Bit_13
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV29 FBFixedControlWord
Bit_14
Application Specific bit from
the Fixed Control Word
0 / 1 C
BV30 FBFixedControlWord
Bit_15
Application Specific bit from
the Fixed Control Word
0 / 1 C
Instance
ID Object Name Description Units
Present Value
Access Type
AV0 Frequency Setpoint Frequency Setpoint Hz R
AV1 Output Frequency Output Frequency Hz R
AV2 Motor Speed Motor Speed Rpm R
AV3 Load (power) Motor Shaft Power Percent R
AV4 Kilowatt Hours total Megawatt Hour Counter
(Total)
kWh R
AV5 Motor Current Motor Current Amps R
AV6 DC link Voltage DC link Voltage Volts R
AV7 Motor Voltage Motor Voltage Volts R
AV8 Unit Temperature Heatsink Temperature
NOT IN SLX -series
° C R
AV9 Motor Torque In % of motor nominal Torque Percent R
AV10 Operating Days Operating Days (resettable) Day R
AV11 Operating Hours Operating Hours (resettable) Hour R
AV12 Kilowatt Hours Kilowatt Hours (resettable) kWh R
AV13 Torque Reference Torque Reference NOT IN SLX
-series
Percent R
AV14 Temperature Rise Calculated motor temperature
100,0% = nominal
temperature of motor
NOT IN SLX -series
Percent R
AV15 FBProcessDataOut1 Application specific -32768.0 to +32767.0
resolution 1.0
R

Table of Contents