6.3.3 MTL5533 - Vibration Transducer Interface
(Reference use only: Terminated product, use 2 x MTL5531)
Two channel
The MTL5533 repeats signals from vibration sensors in a hazardous area, providing outputs
for monitoring systems in the safe area. The interface is compatible with 3-wire eddy-current
probes and accelerometers or 2-wire current sensors, and selection of the mode for each
channel is made with the switches on the side of the module.
Hazardous area Safe area
Vibration
transducer
Vibration
transducer
Vibration
transducer
Vibration
transducer
COM
SIG
V–
COM
SIG
V–
Vs–
Vs+
20 to 35V dc
–ve
0V
Monitor
3-
wire
2
1
3-
wire
2-
wire
5
4
2-
wire
Monitor
–ve
0V
3
6
Ch 1
Ch 2
Ch 1
Ch 2
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Terminal Function
1 Transducer power V– (Ch1)
2 Signal (Ch1)
3 Common (Ch1)
4 Transducer power V– (Ch2)
5 Signal (Ch2)
6 Common (Ch2)
8 Signal output –ve (Ch2)
9 Signal output 0V (Ch2)
11 Signal output –ve (Ch1)
12 Signal output 0V (Ch1)
13 Supply –ve
14 Supply +ve
OFF position
ON position
Ch 1 Ch 2
2-/3-wire transducer setting switches
Mode SW
2-wire (3.3mA) OFF
3-wire (20mA) ON
* Note: When using 2-wire sensors, ensure
that terminals 1 & 2 and 4 & 5 have wiring
links as shown in the wiring diagram above.
WARNING!
To enable adequate heat dissipation from the MTL5533 modules, they
must be installed on the DIN rail with a 10mm space between adjacent
units. Eaton produce the MS010 DIN rail module spacer for this purpose
(packs of 5 - see Section 4.3), and these then enable operation in ambient
temperatures of up to 50°C in vertical or horizontal orientation.
Figure 6.19:
Top label