EasyManua.ls Logo

Eaton Crouse-Hinds MTL5500 Series - PCS45;PCL45 USB Configurator for Temperature Converters

Eaton Crouse-Hinds MTL5500 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INM 5500 Rev 11
50
6.7 Temperature Input module
These modules accept inputs from low-level dc sources such as thermocouples or RTDs in
hazardous areas and converts them into 4/20mA signals to drive safe area loads.
Thermocouples Early burnout detection (EBD)
When EBD is selected, the resistance of the thermocouple circuit is monitored and an alarm is
raised when there is an increase of more than 50W. This enables preventative maintenance to
be conducted on the field installation before the thermocouple actually breaks.
Configuration using PCS45/PCL45USB
Use PCS45 software, in conjunction with the PCL45USB serial link, to configure these modules.
Instructions are contained within the software. See Section 6.9 on page 58 for further details.
All MTL5573 and MTL5575 modules are supplied with the following default configuration.
Input type Type K thermocouple
Linearisation enabled
Units °C
CJ Compensation enabled
Damping value 0 seconds
Smoothing value 0 seconds
Output zero 0°C
Output span 250°C
Tag and description fields blank
Open circuit alarm set high (upscale)
Transmitter failure alarm set low (downscale)
CJ failure alarm set low (downscale)
Line frequency 50Hz
Use PCS45 software, in conjunction with the PCL45USB serial link, to
modify these default values.

Table of Contents