18 EATON CORPORATION Cutler-Hammer Chiller Starter (AMPGARD) Technical Data TD02003003E Effective: October 2006
Type SL 200 Ampere Vacuum Contactor Ratings
TABLE 5. TYPE SL 200 AMPERE VACUUM CONTACTOR RATINGS
TABLE 6. TYPE SL 200 AMPERE VACUUM CONTACTOR SPECIFICATIONS
Time stated in cycles on 60 Hz base.
RATED UTILIZATION
VOLTAGE
2200 TO 2500
VOLTS
3000 TO 3600
VOLTS
3800 TO 4800
VOLTS
6000 TO 6600
VOLTS
Interrupting Rating
NEMA Unfused (E1)
NEMA Fused (E2)
4.5 kA
50 kA, 200 MVA at 2400 V
4.5 kA
50 kA, 285 MVA at 3300 V
4.5 kA
50 kA, 400 MVA at 4600 V
4.5 kA
50 kA, 570 MVA at 6600 V
Application Table
Induction Motor 700 hp 1000 hp 1250 hp 2000 hp
SPECIFICATION RATING
Maximum Insulation Voltage 7200 Volts
Maximum Interrupting Current (3 Operations) 4500 Amperes
Rated Current 200 Amperes Enclosed
IEC Make-Break Capability-AC4
Make
Break
2000 Amperes
1600 Amperes
Short-Time Current
30 Seconds
1 Second
8.7 Milliseconds (.5 Cycle)
1200 Amperes
3000 Amperes
63 kA Peak
Standard Service Altitude -1000 to +2000 Meters
Optional Service Altitudes -3500 to -1001 Meters
+2001 to +5000 Meters
Mechanical Life 2.5 Million Operations
Electrical Life 300,000 Operations
BIL 60 kV (1.2 x 50 Microseconds)
Dielectric Strength (60 Hz) 20 kV (1 Minute)
Closing Time (Energization to Contact Touch) 80 Milliseconds
Opening Time 30 to 330 Milliseconds (Selectable)
Arcing Time 12 Milliseconds (3/4 Cycle) or Less
Pickup Voltage 80% Rated Coil Voltage
Dropout Voltage 60% Rated Coil Voltage
Control Voltages
ac
dc
110/120/220/240 (50/60 Hz)
125
Control Circuit Burden
Closing (ac)/(dc)
Holding (ac)/(dc)
100 V – 125 V, 1 kVA/200 V – 250 V, 1.8 kVA
100 V – 125 V, 40 VA/200 V – 250 V, 50 VA
Auxiliary Contact Rating
Voltage (Maximum)
Continuous Current
Making Capacity (ac)
Making Capacity (dc)
Breaking Capacity (ac)
Breaking Capacity (dc)
600 Volts
10 Amperes
7200 VA
125 VA
720 VA
125 VA
Latch (When Specified)
Mechanical Life
Trip Voltages (dc)
Trip Voltages (ac)
250,000 Operations
24 Volts/125 Volts
110/120 Volts
Minimum Trip Voltage 80% Rated Coil Voltage
Trip Burden
24 Vdc
125 Vdc
110/120 Vac
400 VA
400 VA
400 VA
Trip Time 30 Milliseconds
Weight 60 lbs. (27 kg) (Stab-in/bolt-in)