Available on Catalog Nos. 
and 
5.6 Ground Fault Time Settings 
The ground fault time delay is a flat response with four 
settings 
(I, 
.15, .3, 
.5 
second) available (Figure 12-3).The 
6.1 Functional Field Testing 
A test receptacle is built into each trip unit to allow use of 
the STK2 Test Kit. The Test Kit performs a test of the Long 
Delay, Short Delay and Ground Fault functions. 
6.2.1 Code Requirements 
The National Electrical Code under Article 230
-
95
-
C 
requires that any ground
-
fault protection system be 
performance tested when first installed. The test shall be 
conducted in accordance with approved instructions 
I 
\ 
I 
I\ 
Remove- 
I 
LTest 
Jacks 
Fig. 
11 
Adjustment Switches and Test Points 
5 
3@7 
Short 
Delay Pickup 
(Multiples 
of 
Rated 
Current 
1,) 
Current 
W 
+ 
E 
I 
Ih 
1 
Ilh 
5 
Short Delay Pick
-
up 
(Multiples 
of 
Rated 
Cu 
Current 
irrent) 
Fig. 
12-1 
Short Delay Trip Current Adjustment and Curve 
Details 
Fig. 
12-2 
Short Delay Trip Current and Short Delay Trip 
Time  Adjustment and Curve Details 
Effective 
March 2003
6.2  Performance Testing for Ground Fault Trip Units
I.L. 29C615E
6.0 TESTING
LES3xxxLSG, -LSIG, MES3xxxLSG, and -LSIG
(Instantaneous).  This option is available on Catalog Nos.
I setting gives a trip response with no intentional delay 
breaker. 
matter what rating plug is installed in the circuit 
Note: These ampere values are always the same no 
values listed on the trip unit nameplate and in Table 1.2. 
(see Figure 12-3) and correspond to the fixed ampere 
Five settings ranging from 1 through 5 (xlG) are available 
5.5 Ground Fault Pick-Up Setting 
neous Pickup. 
Delay Pickup (see paragraph 5.2) then becomes Instanta- 
by setting Short Delay Time to "I" (Instantaneous.) Short 
Page 8
300
Courtesy of NationalSwitchgear.com