Page 
9 
I 
’*+ 
I 
L 
t 
L 
Time 
Ms 
Current 
Fig. 12
-
3 Ground Fault Trip Current, and Ground Fault Trip 
Time Adjustments  and Curve Details 
provided with the equipment. 
A 
written record of this test 
shall be made and shall be available to the authority 
having inspection jurisdiction. 
6.2.2 Standards Requirements 
As 
a follow
-
up to the basic performance requirements 
stipulated by the 
N.E.C. 
as stated above, UL Standard 
No. 
1053 requires that certain minimum instructions must 
accompany each ground fault protection system. These 
following statements plus a copy of the test record form 
illustrated in Fig. 16 are shipped with each Digitrip 
RMS 
31 
0 
Trip Unit. 
6.2.3 General Test Instructions 
The interconnected system shall be evaluated in accor
- 
dance with the equipment assembler’s detailed instruc
- 
tions by qualified personnel. 
The polarity of the neutral sensor connections (if used) 
must agree with equipment assembler’s detailed instruc
- 
tions to avoid improper operations following apparently 
correct simulated test operations. Where a question 
exists, consult the specifying engineer and/or equipment 
assembler. 
The grounding points of the system shall be verified to 
determine that ground paths do not exist that would 
bypass the sensors. The use of  high
-
voltage testers and 
resistance bridges may be used. 
.- 
i 
+ 
300\(!& 
8 
Rating Plug Setting (Amperes) 
2x-Ex 
2x-8x  2x.8~ 2x-Ex 
See 
Fig. 
2
-
7 
and 
Fig. 
2-8 
for 
Continuation of Short Time 
Instantaneous Portions of Curves 
Current 
Fig. 13 Optional  Adjustable  Ampere Setting Rating 
Plug Used in 
L 
ES 
Trip Unit 
a 
WARNING 
THERE 
IS 
A HAZARD OF ELECTRICAL SHOCK 
OR 
BURN WHENEVER WORKING IN 
OR 
AROUND 
ELECTRICAL EQUIPMENT. ALWAYSTURN OFF 
POWER SUPPLYING BREAKER BEFORE 
CONDUCTING TESTS. 
Note: Since the Digitrip 
RMS 
31OTrip Units derive 
their operating power from the phase currents, and 
not from the neutral current, passing current through 
the neutral sensor only will not properly test the 
ground fault feature. 
Using a low voltage (0
-
24 volt), high current, 
AC 
source, 
apply a test current of  125% of the Digitrip 
RMS 
310 
Ground 
FaultTrip Unit pick
-
up setting through one phase 
of the circuit breaker, as shown in Fig. 14
-
1 .This should 
cause the breaker to trip in less than 1 second, and 
if 
an 
alarm indicator is supplied, it should operate. Reset the 
breaker and the alarm indicator. Repeat the test on the 
other two phases. 
Effective 
March 2003
EAVN 
I.L. 29C615E
Courtesy of NationalSwitchgear.com