Do you have a question about the Eaton Digitrip RMS 310 and is the answer not in the manual?
Frequency | 50/60 Hz |
---|---|
Category | Electronic Trip Unit |
Voltage Rating | 690 V |
Protection Functions | Ground Fault |
Communication | Modbus |
Functions | Protection |
Protection | Ground Fault |
Display | LCD |
Standards | IEC 60947-2 |
Describes the Digitrip RMS 310 as an electronic trip unit with a custom application specific integrated circuit design.
Test points are provided for functional field testing of the trip unit when connected to a test kit.
States the Digitrip RMS 310 Trip Unit is listed in accordance with UL 489 Standard.
Explains the Digitrip RMS 310 provides a tripping signal using a microprocessor and custom ICs for numeric and logic functions.
Explains the trip unit initiates a trip within two hours for 135% overload and has a 'cooling off' period after trips.
Describes trip initiation for short circuit conditions based on I2t ramp or flat response time delays.
Details how ground fault settings allow selective coordination and mentions an optional Automatic Trip Relay (ATR).
Explains that the rating plug sets the maximum continuous current and settings are multiples of In.
Seven available settings ranging from 2 to 8 multiples of the rating plug amperes (In).
Details I2t ramp configuration or flat response time delays for different catalog numbers.
Explains how to achieve instantaneous pickup by setting Short Delay Time to 'I'.
Eight settings (A-K, excluding G) corresponding to fixed ampere values for ground fault pickup.
Offers four flat response time delay settings for ground fault: instantaneous (I), 0.15, 0.3, and 0.5 seconds.
Lists instruction leaflets for Digitrip RMS 310, 510, 610, and 810 Trip Units.
Lists instruction leaflets and diagrams for R-Frame breakers used with Digitrip RMS Trip Units.