ELC Programming Manual
FOR MORE INFORMATION VISIT: WWW.EATON.COM MN05003003E
2-96
Example:
X7
SPD X1 K1000 D0
SET
M1036
When X7=ON, the parameters of D0 are as follows:
Index Function
+0 Speed detection of X0 signal input = low 16 bits of 32 bits.
+1 Speed detection of X0 signal input = high 16 bits of 32 bits.
+2 Speed detection of X1 signal input = low 16 bits of 32 bits.
+3 Speed detection of X1 signal input = high 16 bits of 32 bits.
+4 Speed detection of X2 signal input = low 16 bits of 32 bits.
+5 Speed detection of X2 signal input = high 16 bits of 32 bits.
+6 Speed detection of X3 signal input = low 16 bits of 32 bits.
+7 Speed detection of X3 signal input = high 16 bits of 32 bits.
+8 Speed detection of X4 signal input = low 16 bits of 32 bits.
+9 Speed detection of X4 signal input = high 16 bits of 32 bits.
+10 Speed detection of X5 signal input = low 16 bits of 32 bits.
+11 Speed detection of X5 signal input = high 16 bits of 32 bits.
+12 Left time of speed detection (unit: ms)
Function Group
Communication Response Delay
Number
D1038
Contents:
1. Data response delay time can be set when the ELC is a Slave in RS-485 communication. Unit
is 0.1ms. 0~10,000 adjustable.
2. For PC/PA/PH/PV, ELCM-PH/PA controllers, by using ELC-Link (Master), D1038 can be set
to send next communication data with delay. (Unit: 1 scan period for ELC-PC/PA/PH, ELCM-
PH/PA, 0.1ms for PV)
Function Group
Constant scan time
Number
M1039, D1039
Contents:
1. When M1039 is ON, program scan time is determined by D1039 (if D1039 is greater than the
maximum scan time). When program finishes executing, it will execute the next scan after the
time set by D1039. If D1039 is less than program scan time, the program scan will complete,
and the scan time will be the normal program scan time.