EasyManua.ls Logo

Eaton ELC-PB - Page 127

Eaton ELC-PB
728 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ELC Programming Manual
FOR MORE INFORMATION VISIT: WWW.EATON.COM MN05003003E
2-98
Function
D1116 Analog output channel 0 (DA 0).
D1117 Analog output channel 1 (DA 1).
D1118
Analog input filter setting (ms).
For ELC-PA controllers, sampling time of analog/digital conversion Sampling time
will be regarded as 5ms If D11185.
For ELCM-PA controllers, sampling time of analog/digital conversion Sampling
time will be regarded as 2ms If D11182.
Function Group
Algorithm Error Flag
Number
M1067~M1068, D1067~D1068
Contents:
Algorithm error flag:
Component Explanation Latched
STOPRUN RUNSTOP
M1067 Algorithm error flag None Clear Latched
M1068 Algorithm error lock flag None Unchanged Latched
D1067 Algorithm error code None Clear Latched
D1068 STEP value of algorithm error None Unchanged Latched
Error code explanation:
D1067
error code
Function
0E18 BCD conversion error
0E19 Divisor is 0
0E1A Usage exceeds limit (include E and F)
0E1B It is negative number after doing radical
0E1C FROM/TO communication error
Function Group
Low Voltage
Number
M1087, D1100
Contents:
1. When the ELC detects LV (Low Voltage) signal, it will check if M1087 is “ON” or not. If M1087
is “ON”, the content in D1100 will be stored in Y0 ~ Y17.
2. Bit0 (LSB) of D1100 corresponds to Y0, bit1 corresponds to Y1, bit8 corresponds to Y10 and
so on.
Function Group
File Register
Number
M1101, D1101~D1103
Contents: