D1495 and D1512 ~ D1527 of the Master, and the data in D1496 ~ D1511 and D1528 ~
D1543 will be written into D200 ~ D215 of the two Slaves.
Master ELC *1 Slave ELC*2
D1480 ~ D1495 D100 ~ D115 of Slave ID#1
D1496 ~ D1511 D200 ~ D215 of Slave ID#1
D1512 ~ D1527 D100 ~ D115 of Slave ID#2
D1528 ~ D1543
D200 ~ D215 of Slave ID#2
3. Assume the data in D for data exchange between Master and Slave before ELC LINK is
enabled (M1350 = OFF) are as the follow:
Master ELC Preset value Slave ELC Preset value
D1480 ~ D1495 K0 D100 ~ D115 of Slave ID#1 K5,000
D1496 ~ D1511 K1,000 D200 ~ D215 of Slave ID#1 K0
D1512 ~ D1527 K0 D100 ~ D115 of Slave ID#2 K6,000
D1528 ~ D1543 K2,000 D200 ~ D215 of Slave ID#2 K0
After ELC LINK is enabled (M1350 = ON), the data in D for data exchange will become:
Master ELC Preset value Slave ELC Preset value
D1480 ~ D1495 K5,000 D100 ~ D115 of Slave ID#1 K5,000
D1496 ~ D1511 K1,000 D200 ~ D215 of Slave ID#1 K1,000
D1512 ~ D1527 K6,000 D100 ~ D115 of Slave ID#2 K6,000
D1528 ~ D1543 K2,000 D200 ~ D215 of Slave ID#2 K2,000
4. The Master ELC has to be ELC-PC/PA/PH/PV, ELCM-PH/PA controllers, and the Slave ELC
can be any ELC controller.
5. There can be maximum 16 Slave ELCs in ELC LINK. See the special Ds in the Master ELC
corresponding to D100 ~ D115 and D200 ~ D215 in every Slave ELC in the tables of special
M and special D.
Write
Read
Read
Write