4-6
1. Alternative Convergence:
This is an OR condition. There is only one
path. Move from S20 to S30 or S21 to S31 or
S22 to S32 to the step point S40 when the
appropriate transition (6 or 7 or 8) is true.
2. Simultaneous Convergence:
This is an AND condition. Move from S30,
S31, and S32 to the step point S40 according
to the same transition condition 6. S30, S31
and S32 must all be active before
transitioning to S40.
Convergence moves from many steps to one.