ELC Programming Manual
For more information visit: www.eaton.com MN05003003E
B-4
Symptom Troubleshooting and Corrective Actions
Output does not
turn on.
Check the corresponding output LED. If the indicator is ON,
1. Check the wiring of the loads.
2. Check if power is properly supplied to the loads.
3. If the wiring is correct but power is not supplied to the load, there is
potentially a fault with the ELC’s output circuit. Contact the Eaton
support center
If the corresponding output LED is off,
1. Monitor the output condition using a programming tool. If the
output monitored is turned Off, recheck your program
2. If the output monitored is on, there is a potential duplicate output
instruction, or a potential fault in the ELC output circuit