ELC Programming Manual
For more information visit: www.eaton.com MN05003003E
B-6
Fault Code Description Action
0E1A Device use is out of range (including index registers E, F)
0E1B negative number after radical expression
0E1C FROM/TO communication error
0F04 Operand word device D register usage exceeds limit
0F05 DCNT Misuse Operand D
0F06 SFTR Misuse Operand
0F07 SFTL Misuse Operand
0F08 REF Misuse Operand
0F09 Improper use of operands of WSFR, WSFL instructions
0F0A Number of TTMR, STMR instruction exceed the range
0F0B Number of SORT instruction exceed the range
0F0C Number of TKY instruction exceed the range
0F0D Number of HKY instruction exceed the range
1000 ZRST Misuse Operand
10EF E and F misuse operand or exceed the usage range
2000 Usage exceed limit (MTR, ARWS, TTMR, PR, HOUR)
Check the D1137
(Error step
number)
Re-enter the
instruction
correctly
Fault Code Description Action
C400 An unrecognized instruction code is being used
C401 Loop Error
C402 LD / LDI continuously use more than 9 times
C403 MPS continuously use more than 9 times
C404 FOR-NEXT exceed 6 levels
C405
STL / RET used between FOR and NEXT
SRET / IRET used between FOR and NEXT
MC / MCR used between FOR and NEXT
END / FEND used between FOR and NEXT
C407 STL continuously use more than 9 times
C408 Use MC / MCR in STL, Use I / P in STL
C409 Use STL/RET in subroutine or interrupt program
C40A Use MC / MCR in subroutine or interrupt program
C40B MC / MCR does not begin from N0 or discontinuously
C40C MC / MCR corresponding value N is different
C40D Use I / P incorrectly
C40E
IRET does not follow by the last FEND command SRET
does not follow by the last FEND command
Select
programming
mode and correct
the identified error