EasyManua.ls Logo

Eaton EMS2 Series - Page 22

Eaton EMS2 Series
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Motor starters
2.5 Layout of devices with I
e
= 9 A
18 EMS2… Electronic motor starter 10/19 MN034003EN www.eaton.com
Example
A motor with the values shown below is to be operated with an EMS2
electronic motor starter.
Questions:
Is operation possible?
How should the motor starter be mounted?
Checks:
Step 1:
Check to see if the motor starter is suitable for the maximum current (56 A).
I
max
= I
Mot
x startup factor = 4.7 A x 8.5 = 39.95 A < 56 A
Step 2:
Which motor current is permissible at an ambient temperature of 55 °C?
( Figure 8, page 17)
in a row: 4A < 4.7A
not permissible!
at a distance of 20 mm: 6.5 A > 4.7 A
permissible!
Conclusion:
The EMS2 motor starter can be used for this application, but must be
mounted with a distance of at least 20 mm between the devices.
Motor:
Power: P
Mot
= 2.2 kW
Rated operational current I
e
at 400 V:
I
Mot
= 4.7 A
Startup factor I
max
/ I
Mot
:8.5
Control panel
temperature:
55 °C

Table of Contents

Related product manuals