7 Technical data
46 EMS2… Electronic motor starter 10/19 MN034003EN www.eaton.com
Connections
Cross-section - control cables EMS2-D(R)O-T-…:
Push in terminals
0.2 mm² - 2.5 mm²
AWG 24 - 14
EMS2-D(R)O-Z-…:
Screw terminals
0.14 mm² - 2.5 mm²
AWG 24 - 14
Screw terminals
0.14 mm² - 2.5 mm²
AWG 26 - 14
Cross-section - power cables
EMS2-D(R)O-T-…:
Push in terminals
0.2 mm² - 2.5 mm²
AWG 24 - 14
EMS2-D(R)O-Z-…:
Screw terminals
0.2 mm² - 2.5 mm²
AWG 24 - 14
Screw terminals
0.2 mm² - 2.5 mm²
AWG 24 - 14
Tightening torque
EMS2-D(R)O(S)-Z-…: 0,5 Nm - 0,6 Nm
(5 lbs-ins - 7 lbs-ins)
EMS2-D(R)O(S)-T-…: –
0.5 Nm - 0.6 Nm
(5 lbs-ins - 7 lbs-ins)
Stripping length
EMS2-D(R)O-T-…: 10 mm
EMS2-D(R)O-Z-: 8 mm
8 mm
Supply of the device / the control inputs
Overvoltage category III III
Supply
Rated control voltage U
S
24 V DC 230 V AC
Range of the control supply voltage 19.2 V DC - 30 V DC 85 V AC - 253 V AC
Rated control current I
S
40 mA 4 mA
Protection against overvoltage
Yes Yes
Protection against polarity reversal
Yes No
Control inputs
Rated actuating voltage U
C
24 V DC 230 V AC
Rated actuating current I
C
5 mA
For devices with safety function:
EMS2-D(R)OS-…-…-24VDC: 10 mA
7 mA
Switching threshold
LOW < 9.6 V DC
HIGH > 19.2 V DC
LOW < 44 V AC
HIGH > 85 V AC
Protection against polarity reversal
Yes No
Typical break time < 30 ms < 70 ms
Size/feature
EMS2-…-24VDC EMS2-…-230VAC

Table of Contents